    ABB INIIT12 Cnet-to-Cnet Remote Transfer Module

    Ask Lasest Price
    Model Number : INIIT12
    Delivery Time : 5-8 working days
    Supply Ability : Subject to availability
    Brand Name : ABB
    • Product Details
    • Company Profile

    ABB INIIT12 Cnet-to-Cnet Remote Transfer Module

    ABB Harmony Rack Communications · INIIR01

    ABB INIIT12 Cnet-to-Cnet Remote Transfer Module

    A remote transfer module used to link a central Cnet with a satellite Cnet through a serial communication path. INIIT12 works with INNIS01 and NTMP01, providing two configurable RS-232-C ports and nonvolatile storage for the transfer application.

    TypeRemote transfer module
    InterfaceCnet-to-Cnet
    AssemblyINIIR01
    BrandABB Bailey
    Talk to a spare-parts specialistMiya Zheng
    Email for quotationsales@amikon.cn
    WhatsApp+86 180 2077 6792
    04 / Product Introduction

    A serial bridge between central and satellite control networks

    The module belongs in an INIIR01 remote interface. Confirm the two Cnet ends, the serial transport equipment and the NTMP01 termination arrangement before ordering or commissioning a spare.

    01

    Central-to-satellite link

    Transfers system data between a central Cnet and a remote Cnet.

    02

    Transport flexibility

    The serial link can pass through a modem, microwave system or compatible transceiver.

    03

    Two serial channels

    Port 1 carries system data; port 2 can carry system data or provide a diagnostic connection.

    Central siteCnet + INNIS01
    →
    Remote transferINIIT12 + NTMP01
    →
    Satellite siteRemote Cnet
    05 / Technical Specifications

    Memory, serial ports, power and installation data

    ModelINIIT12
    Product typeCnet-to-Cnet remote transfer module
    Interface assemblyINIIR01
    Read-only memory256 KB ROM
    Random-access memory512 KB RAM
    Nonvolatile memory256 KB NVRAM
    Power requirement+5 VDC at 2 A
    Power consumption10 W
    Serial interfacesTwo RS-232-C ports
    Selectable serial rateUp to 19.2 kbaud
    Port 1 roleSystem data
    Port 2 roleSystem data or diagnostics
    Termination hardwareNTMP01 multi-function processor termination unit
    Network-interface companionINNIS01
    Configuration controlFunction Code 202 executive block
    MountingOne module-mounting-unit slot
    Operating temperature0 to 70°C (32 to 158°F)
    Relative humidity5% to 90% up to 55°C; 5% to 40% above 55°C, noncondensing
    AltitudeSea level to 3 km (1.86 mi)
    Air qualityNoncorrosive
    ApprovalsFM Class I, Division 2, Groups A–D; CSA ordinary locations
    02 / Remote Link Design

    Match both Cnet endpoints and the serial transport

    A successful remote interface depends on more than the processor card. Both INNIS01 interfaces, termination wiring and the transport equipment must agree on the installed link design.

    01

    Network endpoint

    Each site uses its Cnet interface to present system traffic to the transfer link.

    02

    Serial transport

    NTMP01 terminates the RS-232-C path to the modem, microwave or transceiver equipment.

    03

    Remote endpoint

    The satellite transfer module restores the traffic path to the remote Cnet.

    03 / Configuration & Diagnostics

    Function Code 202 and the two serial ports define operation

    ABB assigns the remote-transfer operating characteristics through Function Code 202. Preserve the configured block specifications before module replacement.

    Commissioning focus

    • Confirm the selected baud rate matches the transport equipment at both ends.
    • Use Port 1 for system data and verify the configured purpose of Port 2.
    • Check DTE/DCE and cabling at NTMP01 before attributing a no-link condition to the module.
    04 / Compatibility & Replacement

    A documented replacement for INIIT02

    ABB's spare-parts material directs INIIT02 users to INIIT12. The change still requires validation of the complete INIIR01 link, termination hardware and configuration.

    1Confirm the legacy partIdentify the installed INIIT02 or INIIT12 marking and capture the cabinet location.
    2Save Function Code 202 settingsKeep the executive block values used for addresses, ports and link behavior.
    3Record transport settingsNote baud rate, modem or transceiver type and DTE/DCE cable arrangement.
    4Check both endsA remote-link fault may originate at either Cnet endpoint or in the transport circuit.
    06 / Applications & Fault Scenarios

    Remote-link symptoms that lead teams to INIIT12

    01

    Satellite Cnet unavailable

    The remote network stops exchanging system data with the central site.

    02

    Link repeatedly resets

    Serial transport, termination, configuration or module health causes an unstable inter-site connection.

    03

    INIIT02 spare replacement

    A site is implementing ABB's documented move to INIIT12 during scheduled maintenance.

    07 / Official Documentation

    INIIT12 manufacturer documents

    ManufacturerDocumentNumber / VersionOfficial link
    ABBHarmony Rack Communications — Data SheetWBPEEUD250001C1, Rev. C1 View document
    ABBHarmony Rack Communications — OverviewWBPEEUS250002C1, Rev. C1 View document
    ABBSymphony Plus Product Catalog2VAA005340, Rev. G View document
    ABBSpring Savings Event — Bailey / Harmony Spares2020 spare-parts brochure View document
    08 / Supply & RFQ

    Inspection, packing and quotation support

    Amikon Service

    InspectionPart identity and agreed test scope
    Export packingAnti-static and impact-protective
    DOA supportPrompt review with photos and evidence
    Warranty & returnsTerms confirmed on the quotation
    09 / FAQ

    INIIT12 questions from buyers and maintenance teams

    What is ABB INIIT12 used for?

    It links a central Cnet and a satellite Cnet through a serial remote-transfer path as part of an INIIR01 interface.

    Which hardware works with ABB INIIT12?

    The documented interface uses INNIS01 for the Cnet connection and NTMP01 for serial termination.

    How many serial ports does ABB INIIT12 provide?

    It provides two RS-232-C ports. Port 1 carries system data; Port 2 can carry system data or serve as a diagnostic port.

    How is ABB INIIT12 configured?

    Its operating characteristics are controlled through the Function Code 202 executive block. Preserve the installed specifications before replacement.

    Does ABB INIIT12 replace ABB INIIT02?

    Yes. ABB spare-parts material identifies INIIT12 as the replacement path for INIIT02.

    What should be checked when ABB INIIT12 shows no remote link?

    Check both Cnet endpoints, INNIS01 status, NTMP01 wiring, DTE/DCE arrangement, baud rate, transport equipment and Function Code 202 settings.

    10 / Multi-brand Spare Parts Also Requested

    Independent procurement references

    These models are separate sourcing references, not substitutes for INIIT12. Compatibility and stock must be confirmed independently.

    210N2272972-01268-6A-IP20311637312863-A01319828-A01332985-C013G3MX2-A4007-ZV13IF722.93IF761.93IF766.93IF771.93IF772.93IF779.9

    No interchangeability, migration or replacement relationship is implied by this list.

    INIIT12 · ABB / Bailey industrial automation spare · Contact Miya Zheng for availability and quotation support.