Sign In | Join Free | My burrillandco.com
Home > ABB PLC >

ABB SPHSS13 Symphony Plus Hydraulic Servo Module

AMIKON LIMITED
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now
    Buy cheap ABB SPHSS13 Symphony Plus Hydraulic Servo Module from wholesalers
     
    Buy cheap ABB SPHSS13 Symphony Plus Hydraulic Servo Module from wholesalers
    • Buy cheap ABB SPHSS13 Symphony Plus Hydraulic Servo Module from wholesalers
    • Buy cheap ABB SPHSS13 Symphony Plus Hydraulic Servo Module from wholesalers
    • Buy cheap ABB SPHSS13 Symphony Plus Hydraulic Servo Module from wholesalers

    ABB SPHSS13 Symphony Plus Hydraulic Servo Module

    Ask Lasest Price
    Model Number : SPHSS13
    Brand Name : ABB
    • Product Details
    • Company Profile

    ABB SPHSS13 Symphony Plus Hydraulic Servo Module

    AMIKON · ABB AUTOMATION SPARE · TECHNICAL PRODUCT NOTE

    SPHSS13

    The ABB SPHSS13 is an HR Series hydraulic servo module for manual or automatic positioning of hydraulic actuators through a servo valve or I/H converter. It supports turbine-valve control, AC or DC LVDT feedback, proportional-only operation and fast closed-loop I/O.

    Type
    HR Series intelligent hydraulic servo module
    System
    ABB Symphony Plus Harmony Rack Turbine Control
    Focus
    HR Series intelligent hydraulic servo module
    Brand
    ABB / Bailey
    Contact: Miya Zheng · sales@amikon.cn · WhatsApp: +86 180 2077 6792
    Email WhatsApp
    01

    Product Introduction

    The ABB SPHSS13 is an HR Series hydraulic servo module for manual or automatic positioning of hydraulic actuators through a servo valve or I/H converter. It supports turbine-valve control, AC or DC LVDT feedback, proportional-only operation and fast closed-loop I/O.

    02

    Technical Specifications

    01LVDT feedback inputs4 analog secondary inputs for two LVDTs, two secondaries per LVDT
    02LVDT input rating24 V peak-to-peak; ±7 VDC common mode; 10 kΩ differential input impedance
    03LVDT excitation outputs2 analog primary outputs
    04Excitation frequency400 Hz to 15 kHz
    05Servo outputs2 protected outputs; a short or open on one does not affect the other
    06Servo mode outputUp to ±300 mA
    07I/H mode output4 to 20 mA or 20 to 160 mA
    08Panel outputs1 scaled position-meter output, 1 unscaled feedback output and 1 test output
    09Contact inputs3 optically isolated 250 VDC inputs for raise, lower and trip bias
    10Hard-manual output1 independent optically isolated 250 VDC open-collector output
    11Input-output responseLess than 2 ms
    12+5 VDC power576 mA typical; 2.88 W typical
    13+15 VDC power15 mA typical; 0.23 W typical
    14-15 VDC power12 mA typical; 0.18 W typical
    15+24 VDC field power335 mA typical; 8.04 W typical from termination
    16Dimensions35.56 mm W × 177.80 mm H × 298.45 mm D (1.40 × 7.00 × 11.75 in)
    17Operating temperature0 to 70°C (32 to 158°F)
    18ConstructionSingle printed circuit board; hot-swap capability stated by ABB
    03

    Compatibility & Replacement

    01

    Original-System Compatibility

    Designed for Symphony Plus Harmony Rack turbine-control applications. ABB states compatibility with BRC300, BRC400 and BRC410 controllers at the documented firmware levels, and use with the existing NKHS03 cable and NTHS03 termination. SPTPS13 speed detection is commonly used with it in governor applications.

    02

    Historical Replacement

    ABB identifies SPHSS13 as the direct replacement for IMHSS03, IMHSS04, IMHSS05, SPHSS03, SPHSS04 and SPHSS05. Revision, controller firmware, function-code database, LVDT type and servo-current selection must still be checked before installation.

    04

    Applications & Fault Scenarios

    • Steam-turbine throttle and control valves, gas-turbine fuel valves, inlet guide vanes and nozzle-angle positioning.
    • Fast PI or proportional-only hydraulic positioning with AC or DC LVDT feedback.
    • Reporting a non-modulating valve position without control, covering the documented SPLPS01-type function.
    • Maintenance searches commonly involve LVDT mismatch, feedback calibration, servo-coil open/short, controller firmware, hard-manual transfer or actuator instability.
    • A failed servo loop may force manual control, prevent turbine startup or cause an unplanned trip, so firmware and loop commissioning checks are part of replacement planning.
    05

    Redundancy & Control

    • Two servo outputs may be used as active outputs or active/standby; output protection isolates a short or open on one channel from the other.
    • Automatic feedback and demodulator calibration, active current limiting and self-resetting fuses are documented enhancements.
    • FC55 supports the documented control modes; verify the installed controller firmware and database before commissioning.
    06

    Configuration & Installation

    • ABB documents use of the existing NKHS03 cable and NTHS03 termination for the replacement path.
    • Confirm AC or DC LVDT topology, excitation, polarity, servo/IH current range, hard-manual contacts and valve travel before hot swap or outage work.
    • Hot-swap capability does not remove the need for an approved turbine-control procedure and a controlled valve-stroke test.
    07

    Diagnostics & Maintenance

    • Use the module's feedback, test and position-meter signals to separate an electronic problem from actuator, LVDT or field-wiring faults.
    • Check controller compatibility, function-code status and output current selection before replacing hardware.
    • Keep the module static-safe and clean, inspect cable/termination integrity and retain commissioning records for subsequent loop comparison.
    08

    Associated Hardware

    • BRC300/BRC400/BRC410 controller at ABB-documented firmware levels.
    • NKHS03 cable and NTHS03 termination.
    • SPTPS13 speed detection module in typical governor applications.
    09

    Official Manufacturer Sources

    01
    ABB · 2VAA005340 en G

    ABB Ability Symphony Plus Product Catalog

    SPHSS13 operating power, LVDT interfaces, servo and I/H outputs, digital I/O, temperature, dimensions and application description.

    02
    ABB · ABB Users Group 2016

    Symphony Plus Lifecycle Updates – SPHSS13

    Direct replacement list, controller compatibility, existing cable and termination use, current range and reliability features.

    10

    Amikon Service

    Test & Packing

    Pre-shipment check, antistatic protection and reinforced packing.

    DOA & Returns

    Prompt review under the written order terms with fault evidence.

    Warranty

    Covers confirmed supply defects during the agreed period.

    Sales Support

    Part-number, revision and system checks before dispatch.

    11

    Request for Quotation

    RFQ checklist

    Send the Part Number, Quantity, Destination, Required Date and Machine/System Model. A clear nameplate photo helps confirm the request.

    12

    Multi-brand Spare Parts Also Requested

    13

    FAQ

    01How should SPHSS13 be installed?
    Confirm controller firmware, FC55 configuration, NKHS03/NTHS03 hardware, LVDT type, current range and valve calibration. Use an approved turbine procedure and complete a controlled travel test before releasing the loop.
    02Which legacy modules can SPHSS13 replace?
    ABB identifies IMHSS03, IMHSS04, IMHSS05, SPHSS03, SPHSS04 and SPHSS05. Revision-specific LVDT arrangements, firmware and configuration must still be verified.
    03What should be configured on SPHSS13?
    Set the required control mode, LVDT excitation and polarity, servo or I/H output, redundant-output behavior, hard-manual contacts and actuator travel parameters to match the original loop design.
    04How should SPHSS13 be maintained and protected from ESD?
    Use grounded ESD controls and antistatic storage. Keep cable and termination connections clean, compare feedback and test outputs during troubleshooting, and retain the commissioned valve-stroke records.
    05What delivery and warranty support is available for SPHSS13?
    Each unit is function-checked where suitable test facilities are available and packed in an antistatic bag with protective cushioning. DOA, return and exchange requests are handled under the written order terms after evidence and technical evaluation. Warranty covers confirmed supply defects during the agreed period, excluding misuse, incorrect installation, ESD damage, improper storage and unauthorized repair.
    06What information is needed for an SPHSS13 RFQ?
    Please provide the Part Number, Quantity, Destination, Required Date and Machine/System Model. The legacy module, controller firmware, termination, LVDT type and output-current range help confirm the correct supply.

    Technical statements are limited to verified ABB/Bailey manufacturer documentation. Installation must follow the plant safety procedure and the documentation for the installed system revision.

    Quality ABB SPHSS13 Symphony Plus Hydraulic Servo Module for sale
    Inquiry Cart 0
    Send your message to this supplier
     
    *From:
    *To: AMIKON LIMITED
    *Subject:
    *Message:
    Characters Remaining: (0/3000)
     
    Find Similar Products By Category: