Sign In | Join Free | My burrillandco.com
Home > ABB PLC >

ABB SPDSI22 Symphony Plus Digital Input Module

AMIKON LIMITED
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now
    Buy cheap ABB SPDSI22 Symphony Plus Digital Input Module from wholesalers
     
    Buy cheap ABB SPDSI22 Symphony Plus Digital Input Module from wholesalers
    • Buy cheap ABB SPDSI22 Symphony Plus Digital Input Module from wholesalers
    • Buy cheap ABB SPDSI22 Symphony Plus Digital Input Module from wholesalers
    • Buy cheap ABB SPDSI22 Symphony Plus Digital Input Module from wholesalers

    ABB SPDSI22 Symphony Plus Digital Input Module

    Ask Lasest Price
    Model Number : SPDSI22
    Brand Name : ABB
    • Product Details
    • Company Profile

    ABB SPDSI22 Symphony Plus Digital Input Module

    AMIKON · ABB AUTOMATION SPARE · TECHNICAL PRODUCT NOTE

    SPDSI22

    The ABB SPDSI22 is a Harmony Rack digital input module with 16 optically isolated channels. Each channel can be configured for the documented DC or AC field-voltage class, making it the HR migration module for several legacy INFI 90 digital input types.

    Type
    16-channel optically isolated digital input module
    System
    ABB Symphony Plus Harmony Rack I/O
    Focus
    16-channel optically isolated digital input module
    Brand
    ABB / Bailey
    Contact: Miya Zheng · sales@amikon.cn · WhatsApp: +86 180 2077 6792
    Email WhatsApp
    01

    Product Introduction

    The ABB SPDSI22 is a Harmony Rack digital input module with 16 optically isolated channels. Each channel can be configured for the documented DC or AC field-voltage class, making it the HR migration module for several legacy INFI 90 digital input types.

    02

    Technical Specifications

    01Input channels16, optically isolated and individually programmable
    02Supported field voltages24 VDC, 48 VDC, 125 VDC or 120 VAC
    03Input current at 125 VDC4.5 mA
    04Input current at 120 VAC6 mA
    05Logic power+5 VDC ±5%, 95 mA typical
    06Operating temperature0 to 70°C (32 to 158°F)
    07Mapped legacy function codeFC84
    08Processor / memory / dimensionsNot stated for this model in the reviewed ABB product documentation
    03

    Compatibility & Replacement

    01

    Original-System Compatibility

    Designed for Symphony Plus Harmony Rack digital input service. The ABB evolution map carries legacy digital-input applications through FC84; exact rack, termination and field-voltage details must be taken from the installed cabinet drawings.

    02

    Historical Replacement

    ABB identifies SPDSI22 as the HR replacement for IMDSI02, IMDSI12, IMDSI13, IMDSI14, IMDSI15 and IMDSI22. For an input-only IMDSM05 migration, ABB requires a dipshunt change and reversed field-wire polarity; a mixed-I/O or Digital Logic Station application has no direct replacement in that mapping.

    04

    Applications & Fault Scenarios

    • Status and alarm inputs from contacts, limit switches, relays, breakers and interlocks.
    • Mixed plant standards where individual channels require documented 24 VDC, 48 VDC, 125 VDC or 120 VAC configuration.
    • Maintenance searches commonly follow a wrong AC/DC or voltage selection, FC84/address mismatch, missing input, field-polarity error, bus fault or termination problem.
    • Loss of interlock or protection indications can block starts, force conservative logic states or extend downtime while the field circuit is proved.
    05

    Configuration & Installation

    • Program every channel for its actual field-voltage class and verify the FC84/module-address mapping.
    • When replacing IMDSI02, note the legacy termination restriction: inputs 7/8 and 15/16 share commons in the mapped arrangement and each pair must use the same voltage source.
    • When migrating an input-only IMDSM05, complete the ABB-specified dipshunt and field-polarity changes before energizing the inputs.
    06

    Diagnostics & Maintenance

    • Compare the module indication and controller point quality with the measured field voltage before replacing the input module.
    • If a whole group is missing, inspect module power, rack communication, address, termination common and cable connection.
    • Preserve the original channel-voltage schedule and use grounded ESD controls during exchange.
    07

    Migration Notes

    • HR mapping covers the listed IMDSI models through SPDSI22.
    • SD-series migration depends on field-voltage class; mixed high- and low-voltage points may require more than one SD module.
    • Mixed IMDSM05 I/O or a Digital Logic Station function requires a separate engineering solution.
    08

    Official Manufacturer Sources

    01
    ABB · 2VAA005340 en G

    ABB Ability Symphony Plus Product Catalog

    SPDSI22 channel count, supported field voltages, input current, logic power and operating temperature.

    02
    ABB · ABB Users Group – Harmony

    Harmony Evolution / HR and SD I/O Mapping

    Legacy IMDSI and IMDSM05 replacement mapping, FC84, wiring changes and SD-series voltage-specific routes.

    09

    Amikon Service

    Test & Packing

    Pre-shipment check, antistatic protection and reinforced packing.

    DOA & Returns

    Prompt review under the written order terms with fault evidence.

    Warranty

    Covers confirmed supply defects during the agreed period.

    Sales Support

    Part-number, revision and system checks before dispatch.

    10

    Request for Quotation

    RFQ checklist

    Send the Part Number, Quantity, Destination, Required Date and Machine/System Model. A clear nameplate photo helps confirm the request.

    11

    Multi-brand Spare Parts Also Requested

    12

    FAQ

    01How should SPDSI22 be installed?
    Confirm the rack slot, address, FC84 configuration, termination and field-voltage class for all 16 channels. Isolate field sources as required and verify polarity and shared-common restrictions before energizing.
    02Can SPDSI22 replace IMDSI02 or IMDSM05 directly?
    ABB maps it as the HR replacement for the listed IMDSI modules. An input-only IMDSM05 migration additionally requires a dipshunt change and reversed field-wire polarity; mixed I/O or Digital Logic Station use is not a direct replacement.
    03What must be configured on SPDSI22?
    Set each channel to the actual 24 VDC, 48 VDC, 125 VDC or 120 VAC class and match the module address and FC84 data to the controller database.
    04How should SPDSI22 be maintained and protected from ESD?
    Use a grounded wrist strap and antistatic packaging. During troubleshooting, prove the field voltage, common, polarity, termination and point quality before removing the module.
    05What delivery and warranty support is available for SPDSI22?
    Each unit is function-checked where suitable test facilities are available and packed in an antistatic bag with protective cushioning. DOA, return and exchange requests are handled under the written order terms after evidence and technical evaluation. Warranty covers confirmed supply defects during the agreed period, excluding misuse, incorrect installation, ESD damage, improper storage and unauthorized repair.
    06What information is needed for an SPDSI22 RFQ?
    Please provide the Part Number, Quantity, Destination, Required Date and Machine/System Model. Include the legacy module number, field-voltage schedule and termination type for migration orders.

    Technical statements are limited to verified ABB/Bailey manufacturer documentation. Installation must follow the plant safety procedure and the documentation for the installed system revision.